Round tubes with No. 40 secondary carriers
Reading the Drawing
M6 hex bolts engage the top slot of the tube and connect it directly to the No. 40 secondary carrier.
Numbered Component Key
Match each number to the label below. Dimensions shown on the drawing are in millimeters unless noted.
- M8 galvanized hanger rod
- No. 40 carrier
- M6 hex bolt
- 50 mm round aluminum tube
- Galvanized hanger rod
- Round aluminum tube
Installation Steps
- Measure the finished elevation required by the ceiling design.
- Establish the installation direction. Drill suspension points in the structural ceiling at no more than 1,200 mm spacing and secure the galvanized hanger rods with expansion anchors.
- Install and level the No. 40 secondary carriers, keeping the elevation consistent and the carriers no more than 1,200 mm apart.
- Insert M6 hex bolts into the top slot of the round aluminum tube. Secure the member to the carrier and adjust the spacing.
- Keep hands clean during installation. Avoid sweat, oil and other contamination on the finished surface.