Strip ceilings are chosen by four things: the visible joint, the installed pitch, the carrier and maintenance access. Two strips with the same face width can need different carriers. This guide compares the five profile families Lianhui makes and turns the choice into a layout, a cutting schedule and a like-for-like quotation.
How do the actual section dimensions compare?
| Profile | Face width → edge height | Sheet thickness by width | Joint and connection |
|---|---|---|---|
| C | 100 / 150 / 200 / 300 → 15 | 100–150: 0.40–0.70; 200: 0.45–0.80; 300: 0.60–0.90 | Low beveled edges; individual strips engage carrier teeth |
| G | 100–150 → 11; 200–300 → 15 | 100–150: 0.40–0.70; 200: 0.45–0.80; 300: 0.60–1.00 | Recessed joint and dedicated G carrier |
| S | 300 → 29 | 0.70–0.95 | Deep square or beveled edge; select the matching version of the carrier |
| U | 85 → 15 | 0.5 or 0.6 | Straight or inclined arrangement, each with its own carrier |
| Hook-on | 150 → 20; 200 → 25; 300 → 29 | 150: 0.50–0.70; 200: 0.60–0.80; 300: 0.70–1.00 | Adjacent folded edges interlock and engage a hook-on carrier |
All five families are available in lengths up to 6,000 mm. Order lengths to suit the room, the supports and the delivery route: long strips mean fewer end joints, while shorter strips are easier to carry through a finished building and to replace later.
Is face width the same as the installed pitch?
Face width identifies the product; installed pitch sets out the ceiling. Pitch is the distance between the same points on neighbouring strips, including the joint or gap. Use the confirmed pitch for setting out and avoid adding a joint allowance twice.
Setting-out: a 2,400 mm zone holds 24 repeats at a 100 mm installed pitch and 16 repeats at 150 mm. Wall alignment, perimeter details and the start line then decide whether the end strips need trimming.
Put lighting rows, air outlets and access positions on the same reflected ceiling plan, and adjust the layout before cutting so that no joint runs through the centre of a light and no perimeter piece ends up too narrow.
How do you choose the joint appearance and prove the carrier fit?
C strips give a tight linear joint. G strips add a deeper recessed joint. S strips have a 29 mm return in square or beveled versions. U strips install straight or inclined. Hook-on strips connect through interlocking folded edges. Each profile ships with its own matching carrier.
Before a bulk order, ask for an assembled sample with two adjacent strips on their carrier. Viewed from below and from the side, it shows the joint, the alignment and how the edges engage, which a loose color chip cannot. Sample production takes 3–5 working days, excluding shipping.
How do you centre a strip field inside a 2,500 mm zone?
For a confirmed installed pitch of 150 mm, sixteen repeats occupy 16 × 150 = 2,400 mm. A 2,500 mm setting-out zone leaves 100 mm, or 50 mm at each side for a centred layout.
Draw the two 50 mm perimeter zones as actual details: a closure, border or approved cut piece. Do not simply call them “half strips”; 50 mm is not half of this 150 mm repeat.
Measure the clear dimension between the setting-out boundaries and deduct any perimeter trim before repeating the calculation. Confirm that the edge detail retains the strip and still allows it to be removed.
| Section | S-Shaped Ceiling, deep square edge; matching square-edge carrier |
|---|---|
| Dimensions | 300 mm face, 29 mm edge, 0.80 mm nominal aluminum sheet |
| Cutting schedule | List each required length and quantity from the coordinated ceiling plan |
| Finish and access | Plain face; selected finish code and grain direction if applicable; access strips identified on plan |
The calculation uses 0.80 mm from the 0.70–0.95 mm S-profile range. Hanger and carrier spacing follow the installation details supplied with the system.
How do you test maintenance access before choosing long strips?
Mark the valves, dampers and cable junctions that need access, and show which strip or access panel is removed to reach each one, in which direction and with what tool.
C and G strips can be removed individually; S strips can be removed within the ceiling field. Demonstrate removal and reinstatement on the installed system at handover.
For replacement strips, send the face width, a dimensioned edge section and a carrier sample or drawing so the new strips match the engagement and joint of the existing ceiling.
How do you convert ceiling area into an orderable cutting schedule?
Area is fine for budgeting; we need lengths and quantities. Count rows from the installed pitch, split each row into stock or cut-to-length pieces, and list end joints, perimeter closures and access strips separately so you can see where offcuts arise.
Sixteen rows, each one 4 m strip, need 64 linear metres. At a 150 mm pitch they cover a nominal 2.4 × 4 m field, or 9.6 m², before perimeter details. Carriers, hangers, end pieces and spare strips are separate line items.
How should end joints be coordinated with lighting and maintenance?
Show where long strips stop or join and how each joint is supported. Aligned end joints look different from staggered ones, so confirm the choice on a sample bay and keep it on the reflected ceiling plan.
Check that full-length strips fit through the finished corridors and lifts. Where they will not, split lengths deliberately and coordinate the extra end joints and carriers.
Which five items should you check before releasing the order?
- Correct profile and edge version, with the matching carrier.
- Confirmed installed pitch and perimeter treatment.
- Length-by-length quantities, separate spares and the end-joint arrangement.
- Lights, air outlets and removable service zones on the same layout.
- Finish (powder, PVDF or wood-grain), color and grain direction.
Why compare quotations on the whole ceiling, not just the strip?
| Package | Compare on the same basis |
|---|---|
| Visible strips | Exact profile, sheet thickness, lengths, finish and plain or perforated face |
| Supporting parts | Matching carriers, connectors, hangers and perimeter pieces; clarify exclusions |
| Special pieces | End joints, service openings, removable access areas and inclined sections |
| Quantities | Installed area versus ordered strip lengths; offcuts and spares listed separately |
For perforated strips, specify the hole pattern, solid borders and acoustic backing; see the perforation and acoustics guide. Full sizes are on the C, G, S, U and hook-on product pages.